WAPA Says St. Thomas and St. John Will Face Thanksgiving Blackouts as Generation Falls Short

WAPA reported about 36 megawatts available against an expected peak of 54 in St. Thomas and St. John. Crews are trying to bring another engine online for Thanksgiving, while St. Croix is expected to have normal generation after propane terminal repairs.

  • Ernice Gilbert
  • November 25, 2026
comments
0 Comments
The Randolph Harley Power Plant in St. Thomas, USVI.

The Randolph Harley Power Plant in St. Thomas, USVI. Photo Credit: ERNICE GILBERT.

ST. THOMAS — The V.I. Water and Power Authority expects to cut power in shifts across St. Thomas and St. John on Thanksgiving Day, with the district’s available generation about 18 megawatts below its expected peak demand and no assurance that another engine will be ready in time for the holiday.

Advertisement

At an emergency board meeting Wednesday, WAPA Chief Executive Officer Karl Knight said the authority would try to limit interruptions on circuits that serve residential areas, but it could not keep every household on through the evening peak. 

Kevin Harrigan, superintendent of the Randolph E. Harley Power Plant, told the board that the district had about 36 megawatts available, compared with an expected peak of about 54. Unit 27 and three first-phase Wärtsilä engines were online. Knight said those three engines were each supplying about 6 megawatts instead of their usual 7 and were overdue for major maintenance after reaching 48,000 operating hours. All four second-phase Wärtsilä engines were out of service.

WAPA is looking at whether Engine 6 can safely return in time to reduce the Thanksgiving outages, but Harrigan said its inspection was not complete. Engine 4 also needed further inspection. Crews were reassembling Engine 5 and hoped to finish over the weekend or by Monday. Knight said Wärtsilä had indicated that Engine 7 could return around Dec. 7 by refurbishing its existing turbochargers, earlier than WAPA had originally anticipated. None of those targets is a confirmed return to service.

Advertisement

The Wednesday briefing clarified the status of Engines 4 and 6 after Knight told lawmakers Monday that crews had repaired both. He told the board that problems had recurred after repairs, particularly involving fuel injectors, and that WAPA and Wärtsilä were still working to identify the underlying cause. WAPA expects a new operations and maintenance agreement to begin shifting more of that work to Wärtsilä on Dec. 1.

The district already suffered a widespread blackout Nov. 18, when an operating unit tripped and the remaining generators could not carry the load. On Monday, Knight also told lawmakers that WAPA was exploring a six-month power ship lease that could add at least 30 megawatts at Krum Bay. The proposal would cost $2.85 million upfront, plus electricity charges, and funding remained under discussion.

St. Croix expects a different Thanksgiving

Knight said WAPA expected normal generation on St. Croix on Thanksgiving after the Richmond Power Plant returned to normal operations. In its Tuesday update, WAPA had attributed prolonged outages to emergency work at the propane terminal and a limited diesel supply, without identifying the failed equipment. On Wednesday, WAPA told the board that a defective control panel had triggered the terminal’s emergency shutdown. The utility expected a report within 48 hours on what caused the failure.

The loss of the terminal took propane-only generators out of service and forced WAPA to rely on diesel. Knight said the authority would increase fuel deliveries by truck to build a reserve sufficient for at least five days of diesel-only generation. WAPA also reduced water production by about 1 million gallons Tuesday to free up electricity for customers. Water production had returned to normal in both districts by Wednesday’s meeting, Knight said, though WAPA was still investigating low pressure in parts of western St. Croix.

Advertisement

WAPA urged St. Thomas and St. John customers to conserve electricity and check its outage advisories for schedule changes. Its business offices will be closed Thursday, but customers can report outages through 24-hour dispatch at 340-774-3552 or 340-773-2250, option 4.